LA 16 ASR

Techncial Specification



Model numberLA 16ASR
Height mm 1570
Width mm 1550
Depth mm 850
Temperature operating limits for heating water / Air 55 °C / -20 °C
Temperature operating limits for air -20 °C to 35 °C
Temperature operating limits for cooling 15 °C / 40 °C
Heat output / COP at A-7/W35* kW/- 10,60 / 3,00
Heat output / COP at A+2/W35* kW/- 12,80 / 3,40
Heat output / COP at A+7/W35* kW/- 15,10 / 3,80
Heat output / COP at A+10/W35* kW/- 16,70 / 4,10
Cooling capacity / COP at A+27/W18* kW/- 16,40 / 2,80
Cooling capacity / COP at A+35/W8* kW/- 11,10 / 2,10
Electrical nominal power consumption at A+2/W35 kW 3,00
Sound power level db(A) 64
Sound pressure level at a distance of 10 m (air outlet side) db(A) 34
Sound pressure level at a distance of 1 m (air outlet side) db(A) 51
Refrigerant R404A kg 5,70
Flow rate (heat source) m³/h 4000
Heating water flow rate with an int. pressure differential of m³/h / Pa 1.4 / 4500
Weight (incl. packing) kg 289
Control voltage V 230
Supply voltage 3/PE~400V, 50 Hz
Starting current with soft starterFuse A 25
Fuse A 20
Defrosting / type of defrosting A / -- Reverse cycle
Device connections for heating 1"