RENEWABLE SOLUTIONS - AIR SOURCE - HEATING & COOLING

LA MR range

Technical Specification


Model numberLA 6MRLA 8MRLA 10MR
Temperature operating limits for heating water / air 60 °C / -20 °C 60 °C / -20 °C 60 °C / -20 °C
Temperature operating limits for air -20 °C to 35 °C -20 °C to 35 °C -20 °C to 35 °C
Temperature operating limits for cooling 15 °C / 40 °C 15 °C / 40 °C 15 °C / 40 °C
Heat output / COP at A-7/W35* kW/- 4,60 / 2,65 5,60 / 2,50 6,20 / 2,60
Heat output / COP at A+2/W35* kW/- 5,50 / 3,00 6,80 / 3,00 7,70 / 3,10
Heat output / COP at A+7/W35* kW/- 6,10 / 3,30 7,40 / 3,40 8,50 / 3,40
Heat output / COP at A+10/W35* kW/- 6,60 / 3,65 8,00 / 3,60 9,00 / 3,70
Cooling capacity / COP at A+27/W18* kW/- 8,55 / 4,50 10,50 / 4,50 12,50 / 4,30
Cooling capacity / COP at A+35/W8* kW/- 6,40 / 2,70 7,70 / 2,90 9,00 / 2,90
Electrical nominal power consumption at A+2/W35 kW 1,90 2,30 2,50
Sound power level db(A) 70 71 71
Sound pressure level at a distance of 10 m (air outlet side) db(A) 45 46 46
Refrigerant R407C kg 1,50 2,30 2,70
Dimensions (W x D x H)** mm 1270 x 670 x 860 1270 x 670 x 860 1270 x 670 x 860
Weight (incl. packing) kg 159 165 170
Control voltage V 230 230 230
Supply voltage 1/N/PE~230V, 50Hz 1/N/PE~230V, 50Hz 1/N/PE~230V, 50Hz
Starting current with soft starter A 26 32 38
Fuse A 20 20 25
Defrosting / type of defrosting A / -- Reverse cycle Reverse cycle Reverse cycle
Device connections for heating 1" 1" 1"

* The specified values have the following meaning, e.g. A+2/W35: heat source temperature +2 °C, heat outlet temperature 35 °C.
** Please note that additional space is required for pipe connections, operation and maintenance.

Name and Registered Office: Dimplex (UK) Limited, Millbrook House, Grange Drive, Hedge End, Southampton, Hants, SO30 2DF, United Kingdom.
Company No.1313016 EEE Producer Registration Number – WEE/GE0057TS