LI TE range

Technical Specification


Model numberLI 16TELI 20TE LI 24TE LI 28TE
Dimensions (W x D x H)** mm 750 x 875 x 1570 750 x 875 x 1570 750 x 1025 x 1710 750 x 1025 x 1710
Temperature operating limits for heating water / Air 58 °C / -25 °C 58 °C / -25 °C 58 °C / -25 °C 58 °C / -25 °C
Temperature operating limits for air -25 °C to 35 °C -25 °C to 35 °C -25 °C to 35 °C -25 °C to 35 °C
Heat output / COP at A-7/W35* kW/- 9,80 / 2,60 1 compressor:
7,00 / 2,50
2 compressors:
12,40 / 2,70
1 compressor:
8,90 / 2,60
2 compressors:
16,10 / 2,70
1 compressor:
9,90 / 2,40
2 compressors:
19,10 / 2,70
Heat output / COP at A+2/W35* kW/- 12,20 / 3,20 1 compressor:
9,30 / 3,20
2 compressors:
14,90 / 3,10
1 compressor:
10,90 / 3,00
2 compressors:
19,20 / 3,20
1 compressor:
12,80 / 3,00
2 compressors:
22,30 / 3,00
Heat output / COP at A+7/W35* kW/- 15,40 / 3,70 1 compressor:
9,80 / 3,20
2 compressors:
16,60 / 3,10
1 compressor:
13,10 / 3,40
2 compressors:
24,80 / 3,60
1 compressor:
14,20 / 3,10
2 compressors:
25,80 / 3,40
Heat output / COP at A+10/W35* kW/- 16,10 / 3,80 1 compressor:
10,30 / 3
2 compressors:
17,80 / 3,30
1 compressor:
14,10 / 3,50
2 compressors:
26,60 / 3,80
1 compressor:
14,70 / 3,10
2 compressors:
29,10 / 3,60
Electrical nominal power consumption at A+2/W35 kW 3,81 4,90 6,10 7,40
Sound power level db(A) 57 58 62 62
Sound pressure level at a distance of 1 m (air outlet side) db(A) 52 54 58 58
Refrigerant R404A kg 3,10 3,70 4,20 4,30
Flow rate (heat source) at ext. pressure differential m³/h / Pa 4000 / 25.0 5500 / 25.0 8000 / 25.0 8000 / 25.0
Heating water flow rate with an int. pressure differential of m³/h / Pa 1.4 / 4500 1.8 / 6500 2.3 / 5900 2.3 / 5900
Weight (incl. packing) kg 235 255 310 314
Control voltage V 230 230 230 230
Supply voltage 3/N/PE~400 V, 50 Hz 3/PE~400V, 50 Hz 3/PE~400V, 50 Hz 3/PE~400V, 50 Hz
Starting current with soft starter A 25 23 24 25
Fuse A 20 20 25 25
Defrosting / type of defrosting A / -- Reverse cycle Reverse cycle Reverse cycle Reverse cycle
Device connections for heating 1 1/4" 1 1/4" 1 1/4" 1 1/4"

* The specified values have the following meaning, e.g. A+2/W35: heat source temperature +2 °C, heat outlet temperature 35 °C.
** Please note that additional space is required for pipe connections, operation and maintenance.

Name and Registered Office: Dimplex - a division of the GDC Group, Millbrook House, Grange Drive, Hedge End, Southampton, Hants, SO30 2DF, United Kingdom.
Company No.1313016 EEE Producer Registration Number WEE/GE0057TS
WEEE Distributor Take Back Scheme - Registration ID: 6131
This is an official website of GDC Group Limited. The GDC Group manages the Dimplex brand.
Neither the GDC Group nor Dimplex are associated with any other website containing the Dimplex brand name