LIH TE range
Technical Specification

Technical data
| Model number | LIH 22TE | LIH 26TE | |
| Height | mm | 1710 | 1710 |
| Width | mm | 750 | 750 |
| Depth | mm | 1025 | 1025 |
| Temperature operating limits for heating water / air | 75 °C / -25 °C | 75 °C / -25 °C | |
| Temperature operating limits for air | -25 °C to 35 °C | -25 °C to 35 °C | |
| Heat output / COP at A-7/W35* | kW/- | 11,00 / 2,60 | 13,00 / 2,80 |
| Heat output / COP at A+2/W35* | kW/- | 13,60 / 3,10 | 15,90 / 3,20 |
| Heat output / COP at A+7/W35* | kW/- | 15,40 / 3,40 | 19,80 / 3,80 |
| Heat output / COP at A+10/W35* | kW/- | 16,50 / 3,50 | 20,40 / 3,90 |
| Electrical nominal power consumption at A+2/W35 | kW | 4,40 | 5,00 |
| Refrigerant R404A / R134A | kg | 2,70 | 3,70 |
| Flow rate (heat source) at ext. pressure differential | m³/h / Pa | 8000 / 25.0 | 8000 / 25.0 |
| Heating water flow rate with an int. pressure differential of | m³/h / Pa | 1.8 / 3700 | 2.1 / 3000 |
| Weight (incl. packing) | kg | 370 | 377 |
| Control voltage | 230 | 230 | |
| Supply voltage | V | 3/PE~400V, 50 Hz | 3/PE~400V, 50 Hz |
| Starting current with soft starter | A | 25 | 30 |
| Fuse | A | 25 | 25 |
| Defrosting / type of defrosting | A / -- | Reverse cycle | Reverse cycle |
| Device connections for heating | 1 1/4" | 1 1/4" | |
* The specified values have the following meaning, e.g. A+2/W35: heat source temperature +2 °C, heat outlet temperature 35 °C.
** Please note that additional space is required for pipe connections, operation and maintenance.
Name and Registered Office: Dimplex - a division of the GDC Group,
Millbrook House, Grange Drive, Hedge End, Southampton, Hants, SO30 2DF,
United Kingdom.
Company No.1313016
EEE Producer Registration Number WEE/GE0057TS
WEEE Distributor Take
Back Scheme - Registration ID: 6131
This is an official website of
GDC Group Limited. The GDC Group manages the Dimplex brand.
Neither
the GDC Group nor Dimplex are associated with any other website
containing the Dimplex brand name