RENEWABLE SOLUTIONS - AIR SOURCE - SWIMMING POOL HEATING

LAS TT range


Technical Specification

Model numberLAS 22TT
Temperature operating limits for pool water flow / return flow to 10 °C / from 40 °C
Heat output / power consumption at A+20/W24* kW / kW 22,30 / 4,40
Heat output / power consumption at A+15/W24* kW / kW 20,30 / 4,30
Heat output / power consumption at A+10/W24* kW / kW 18,10 / 4,20
Sound power level db(A) 71
Sound pressure level at a distance of 10 m (air outlet side) db(A) 46
Pool water flow rate at an internal pressure differential of m³/h / Pa 2,5 / 8000
Refrigerant R407C kg 2,50
Dimensions (W x D x H)** mm 1270 x 670 x 860
Weight (incl. packing) kg 162
Electrical nominal power consumption at A15/W32 kW 5.10
Control voltage V 230
Supply voltage 3/PE~400V, 50 Hz
Starting current with soft starter A 25
Fuse A 16
Nominal current at A+15/W32 A 10,0
Defrosting / type of defrosting A / -- Electrical

* The specified values have the following meaning, e.g A20/W24: heat source temperature 20 °C, heat outlet temperature 24 °C.
** Please note that additional space is required for pipe connections, operation and maintenance.


Name and Registered Office: Dimplex (UK) Limited, Millbrook House, Grange Drive, Hedge End, Southampton, Hants, SO30 2DF, United Kingdom.
Company No.1313016 EEE Producer Registration Number – WEE/GE0057TS