RENEWABLE SOLUTIONS - GROUND SOURCE - HEATING
SI MEK range
Technical Specification

| Model number | SI 11 MEK | SI 16 MEK | |
| Temperature operating limits for heating water | Up to 58 °C | Up to 58 °C | |
| Temperature operating limits for brine | -5 °C to 25 °C | -5 °C to 25 °C | |
| Heat output / COP at B0/W50* | kW/- | 11,30 / 3,00 | 15,50 / 2,90 |
| Heat output / COP at B0/W35* | kW/- | 11,80 / 4,40 | 15,80 / 4,20 |
| Electrical nominal power consumption at B0/W35 | kW | 2,66 | 3,77 |
| Refrigerant R407C | kg | 2,00 | 2,30 |
| Flow rate (heat source) at ext. pressure differential | m³/h / Pa | 3.0 / 13000 | 3.5 / 13000 |
| Heating water flow rate with an int. pressure differential of | m³/h / Pa | 1.00 / 3500 | 1.30 / 3500 |
| Dimensions (W x D x H)** | mm | 652 x 688 x 1110 | 652 x 653 x 1110 |
| Weight (incl. packing) | kg | 191 | 203 |
| Control voltage | V | 230 | 230 |
| Supply voltage | 1/N/PE~230V, 50Hz | 1/N/PE~230V, 50Hz | |
| Starting current with soft starter | A | 38 SA | 50 SA |
| Fuse | A | 25 | 32 |
| Device connections for heating | 1 1/4" | 1 1/4" | |
| Device connections for heat source | 1 1/4" | 1 1/4" | |
* The specified values have the following meaning, e.g. B0/W35: heat
source temperature 0°C, heat outlet temperature 35°C.
**
Please note that additional space is required for pipe connections,
operation and maintenance.
Name and Registered Office: Dimplex (UK) Limited, Millbrook House,
Grange Drive, Hedge End, Southampton, Hants, SO30 2DF, United Kingdom.
Company
No.1313016
EEE Producer Registration Number – WEE/GE0057TS