SI MER range

Technical Specification

Model number SI 5MERSI 7MERSI 9MERSI 11MER
Dimensions (W x D x H)** mm 650 x 462 x 805 650 x 462 x 805 650 x 462 x 805 650 x 462 x 805
Temperature operating limits for heating water Up to 58 °C Up to 58 °C Up to 58 °C Up to 58 °C
Temperature operating limits for brine -5 °C to 25 °C -5 °C to 25 °C -5 °C to 25 °C -5 °C to 25 °C
Temperature operating limits for cooling 5 °C / 25 °C 5 °C / 25 °C 5 °C / 25 °C 5 °C / 25 °C
Heat output / COP at B0/W50* kW/- 4,80 / 2,70 6,20 / 2,70 8,80 / 2,80 11,30 / 2,90
Heat output / COP at B0/W35* kW/- 4,90 / 3,90 6,40 / 3,80 9,30 / 4,00 11,60 / 4,10
Cooling capacity / COP at B+10/W8* kW/- 5,40 / 5,60 7,00 / 5,50 9,90 / 5,60 11,60 / 5,70
Cooling capacity / COP at B+10/W18* kW/- 6,80 / 6,70 8,80 / 6,60 12,40 / 6,70 14,10 / 6,50
Electrical nominal power consumption at B0/W35 kW 1,25 1,68 2,30 2,80
Refrigerant R407C kg 0,90 0,90 1,25 1,60
Flow rate (heat source) at ext. pressure differential m³/h / Pa 1.2 / 16000 1.7 / 29500 2.3 / 25000 3.0 / 24000
Heating water flow rate with an int. pressure differential of m³/h / Pa 0.45 / 1900 0.60 / 3300 0.75 / 2300 1.00 / 4100
Weight (incl. packing) kg 115 117 124 128
Control voltage V 230 230 230 230
Supply voltage 1/N/PE~230V, 50Hz 1/N/PE~230V, 50Hz 1/N/PE~230V, 50Hz 1/N/PE~230V, 50Hz
Starting current with soft starter A 24 SA 26 SA 38 38
Fuse A 16 16 20 25
Device connections for heating 1 1/4" 1 1/4" 1 1/4" 1 1/4"
Device connections for heat source 1 1/4" 1 1/4" 1 1/4" 1 1/4"

* The specified values have the following meaning, e.g. B0/W35: heat source temperature 0 °C, heat outlet temperature 35 °C.
** Please note that additional space is required for pipe connections, operation and maintenance.

Name and Registered Office: Dimplex - a division of the GDC Group, Millbrook House, Grange Drive, Hedge End, Southampton, Hants, SO30 2DF, United Kingdom.
Company No.1313016 EEE Producer Registration Number WEE/GE0057TS
WEEE Distributor Take Back Scheme - Registration ID: 6131
This is an official website of GDC Group Limited. The GDC Group manages the Dimplex brand.
Neither the GDC Group nor Dimplex are associated with any other website containing the Dimplex brand name