RENEWABLE SOLUTIONS - GROUND SOURCE - HEATING AND COOLING

SI TER range

Technical Specification



Model number SI TER
Temperature operating limits for heating water Up to 55 °C
Temperature operating limits for brine -5 °C to 25 °C
Heat output / COP at B0/W50* 1 compressors: 33,30 / 2,80
2 compressors: 69,80 / 2,90
Heat output / COP at B0/W35* 1 compressors: 35,10 / 3,80
2 compressors: 65,30 / 3,5
Cooling capacity / COP at B+10/W8* 86,60 / 6,10
Cooling capacity / COP at B+10/W18* 98,20 / 6,30
Electrical nominal power consumption at B0/W35 18,86
Sound pressure level at a distance of 1 m (air outlet side) 54
Refrigerant R404A 16,10
Flow rate (heat source) at ext. pressure differential 20.5 / 17800
Heating water flow rate with an int. pressure differential of 11.50 / 7300
Dimensions (W x D x H)** 1350 x 750 x 1890
Weight (incl. packing) 607
Control voltage 230
Supply voltage 3/PE~400V, 50 Hz
Starting current with soft starter 105
Fuse 63
Device connections for heating 2"
Device connections for heat source 2 1/2"

* The specified values have the following meaning, e.g. B0/W35: heat source temperature 0 °C, heat outlet temperature 35 °C.
** Please note that additional space is required for pipe connections, operation and maintenance.

Name and Registered Office: Dimplex (UK) Limited, Millbrook House, Grange Drive, Hedge End, Southampton, Hants, SO30 2DF, United Kingdom.
Company No.1313016 EEE Producer Registration Number – WEE/GE0057TS