RENEWABLE SOLUTIONS - WATER SOURCE

WI CS range

Technical Specification


Model number WI 40CSWI 90CS
Temperature operating limits for heating water / Cold water 55 °C / 7 °C 55 °C / 7 °C
Temperature operating limits for water kW/- 7 °C to 25 °C 7 °C to 25 °C
Heat output / COP at W10/W50* kW/- 1 compressors:
20,60 / 3,80
2 compressors:
43,00 / 4,00
1 compressors:
45,80 / 4,00
2 compressors:
88,10 / 3,80
Heat output / COP at W10/W35* kW 1 compressors:
23,40 / 5,90
2 compressors:
44,40 / 5,70
1 compressors:
49,80 / 5,90
2 compressors:
91,20 / 5,40
Electrical nominal power consumption at W10/W35 db(A) 7,81 16,97
Sound power level kg 59 70
Refrigerant R407C m³/h / Pa 6,70 15,00
Flow rate (heat source) at ext. pressure differential m³/h / Pa 9.5 / 17500 20.0 / 19000
Heating water flow rate with an int. pressure differential of mm 3.50 / 14000 8.00 / 13000
Dimensions (W x D x H)** kg 1480 x 890 x 830 1480 x 890 x 830
Weight (incl. packing) V 309 460
Control voltage 230 230
Supply voltage 3/PE~400V, 50 Hz 3/PE~400V, 50 Hz
Starting current with soft starter A 26 SA 60 SA
Fuse A 35 63
Device connections for heating 1 1/4" 2"

* The specified values have the following meaning, e.g. W10/W35: heat source temperature 10 °C, heat outlet temperature 35 °C.
** Please note that additional space is required for pipe connections, operation and maintenance.

Name and Registered Office: Dimplex (UK) Limited, Millbrook House, Grange Drive, Hedge End, Southampton, Hants, SO30 2DF, United Kingdom.
Company No.1313016 EEE Producer Registration Number – WEE/GE0057TS