WI CS range

Technical Specification


Model number WI 40CSWI 90CS
Dimensions (W x D x H)** mm 1480 x 890 x 830 1480 x 890 x 830
Temperature operating limits for heating water / Cold water 55 °C / 7 °C 55 °C / 7 °C
Temperature operating limits for water kW/- 7 °C to 25 °C 7 °C to 25 °C
Heat output / COP at W10/W50* kW/- 1 compressors:
20,60 / 3,80
2 compressors:
43,00 / 4,00
1 compressors:
45,80 / 4,00
2 compressors:
88,10 / 3,80
Heat output / COP at W10/W35* kW 1 compressors:
23,40 / 5,90
2 compressors:
44,40 / 5,70
1 compressors:
49,80 / 5,90
2 compressors:
91,20 / 5,40
Electrical nominal power consumption at W10/W35 db(A) 7,81 16,97
Sound power level kg 59 70
Refrigerant R407C m³/h / Pa 6,70 15,00
Flow rate (heat source) at ext. pressure differential m³/h / Pa 9.5 / 17500 20.0 / 19000
Heating water flow rate with an int. pressure differential of mm 3.50 / 14000 8.00 / 13000
Weight (incl. packing) V 309 460
Control voltage 230 230
Supply voltage 3/PE~400V, 50 Hz 3/PE~400V, 50 Hz
Starting current with soft starter A 26 SA 60 SA
Fuse A 35 63
Device connections for heating 1 1/4" 2"

* The specified values have the following meaning, e.g. W10/W35: heat source temperature 10 °C, heat outlet temperature 35 °C.
** Please note that additional space is required for pipe connections, operation and maintenance.

Name and Registered Office: Dimplex - a division of the GDC Group, Millbrook House, Grange Drive, Hedge End, Southampton, Hants, SO30 2DF, United Kingdom.
Company No.1313016 EEE Producer Registration Number WEE/GE0057TS
WEEE Distributor Take Back Scheme - Registration ID: 6131
This is an official website of GDC Group Limited. The GDC Group manages the Dimplex brand.
Neither the GDC Group nor Dimplex are associated with any other website containing the Dimplex brand name